The first scram accrued on June 5. Did TVA throttle their employees from discovering these problems before start-up?
Power Reactor | Event Number: 52026 |
Facility: WATTS BAR Region: 2 State: TN Unit: [ ] [2] [ ] RX Type: [1] W-4-LP,[2] W-4-LP NRC Notified By: MATTHEW MILLER HQ OPS Officer: DANIEL MILLS | Notification Date: 06/20/2016 Notification Time: 17:19 [ET] Event Date: 06/20/2016 Event Time: 15:40 [EDT] Last Update Date: 06/20/2016 |
Emergency Class: NON EMERGENCY 10 CFR Section: 50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION | Person (Organization): BINOY DESAI (R2DO) |
Unit | SCRAM Code | RX CRIT | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
2 | A/R | Y | 32 | Power Operation | 0 | Hot Standby |
AUTOMATIC REACTOR TRIP "On June 20, 2016 at 1540 EDT, Watts Bar Nuclear Plant Unit 2 reactor tripped due to [reaching the] automatic Lo-Lo steam generator trip [setpoint] on [the] #4 steam generator. Concurrent with the reactor trip the Auxiliary Feedwater system actuated as designed. "All control and shutdown rods fully inserted. All safety systems responded as designed. The unit is currently stable in Mode 3, with decay heat removal via Auxiliary Feedwater and main steam dump systems. The station is in a normal shutdown electrical alignment. "The cause is currently under investigation. "This is being reported under 10 CFR 50.72(b)(3)(iv)(A) and 10 CFR 50.72 (b)(2)(iv)(B). "The NRC Senior Resident has been notified." There was no effect on Unit 1. |