Wednesday, September 11, 2019

Browns Ferry: Operators Denied Access To Safety Systems

Well, this is what you would see in a EMP bomb?
Power Reactor Event Number: 54266
Facility: BROWNS FERRY
Region: 2     State: AL
Unit: [1] [2] [3]
RX Type: [1] GE-4,[2] GE-4,[3] GE-4
NRC Notified By: RYAN GRIMME
HQ OPS Officer: THOMAS KENDZIA
Notification Date: 09/11/2019
Notification Time: 03:10 [ET]
Event Date: 09/10/2019
Event Time: 19:34 [CDT]
Last Update Date: 09/11/2019
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(ii)(B) - UNANALYZED CONDITION
Person (Organization):
FRANK EHRHARDT (R2DO)

Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation
3 N Y 100 Power Operation 100 Power Operation

Event Text

UNANALYZED CONDITION DUE TO LIGHTNING STRIKE

"A lightning strike occurred at approximately 1502 CDT on 09/10/2019, and a resulting power surge damaged some of the security door card reader system equipment. However, this did not affect access to plant areas for personnel who were already within protected area. At 1830 on 09/10/2019, it was discovered that some of the oncoming night shift personnel could not access particular areas that required the use of security card readers. Extent of condition check at 1934 on 09/10/2019 determined that access to 1A and 3A Electric Board Rooms, which contain remote shutdown panels and Fire Safe Shutdown equipment. was prohibited for the night shift personnel. This condition is reportable under 10 CFR 50.72(b)(3)(ii)(B) - Any event or condition that results in the nuclear power plant being in an unanalyzed condition that significantly degrades plant safety. Access was restored to all plant areas at 2106 on 9/10/2019. No plant events occurred during the time frame that the 1A & 3A Electric Board Rooms inaccessible that would have required access to these areas.

"The NRC Resident Inspector has been notified."