Power Reactor Event Number: 52443 Facility: COLUMBIA GENERATING STATION
Region: 4 State: WA
Unit: [2] [ ] [ ]
RX Type: [2] GE-5
NRC Notified By: DAVID PORTER
HQ OPS Officer: BETHANY CECERENotification Date: 12/19/2016
Notification Time: 07:39 [ET]
Event Date: 12/18/2016
Event Time: 23:20 [PST]
Last Update Date: 12/19/2016Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
50.72(b)(3)(ii)(A) - DEGRADED CONDITIONPerson (Organization):
RAY KELLAR (R4DO)Event Text
Unit SCRAM Code RX CRIT Initial PWR Initial RX Mode Current PWR Current RX Mode 2 N N 0 Hot Shutdown 0 Hot Shutdown
UNISOLABLE LEAK ON HIGH PRESSURE CORE SPRAY
"On December 18, 2016 at 2320 [PST], a leak was discovered on the High Pressure Core Spray (HPCS) system minimum flow line. The leak is located at a bolted flange downstream of the manual isolation valve HPCS-V-53. The location of the leak is not isolable from the suppression pool. This provides a direct path from inside the Primary Containment to the Reactor Building.
"High Pressure Core Spray system is a single train Emergency Core Cooling System (ECCS) system, therefore inoperability is reportable per 10 CFR 50.72(b)(3)(v)(D).
"Based on the location of the leak, Primary Containment integrity is compromised. Primary Containment was declared inoperable and is reportable per 10 CFR 50.72(b)(3)(ii)(A).
"The cause of the leak is under investigation. Actions are underway to cool down and enter MODE 4."
The licensee has notified the NRC Resident Inspector.